Cross Connection Policy
SECTION
1: PURPOSE
The purpose
of this Policy is:
- To protect the public water supply against actual
or potential contamination that may occur within a water
users premises because of some undiscovered or
unauthorized cross connection on the premises;
- To eliminate existing connections between drinking
water systems and other sources of water that are not
approved as safe and potable for human consumption;
- To eliminate cross-connections between drinking water
systems and sources of contamination;
- To prevent the making of cross-connections in the
future.
These regulations
are adopted pursuant to the State of California Administrative
Code, Title 17 Public Health entitled Regulations
Relating to Cross-Connections. It is unlawful for
any person, firm, or corporation at any time to make or
maintain or cause to be made or maintained, temporarily
or permanently, for any period of time whatsoever, any
cross-connection between plumbing pipes or water fixtures
being served with water by the Association water system
and any other source of water supply or to maintain any
sanitary fixture or other appurtenances or fixtures which,
by reason of their construction, may cause or allow backflow
of water or other substances into the water supply system
of the Association and/or the service of water pipes or
fixtures of any consumer of the Association.
SECTION
2: DEFINITIONS
A. Air-Gap Separation:
The term air-gap separation means a physical
break between a supply pipe and a receiving vessel. The
air-gap shall be at least double the diameter of the supply
pipe measured vertically above the top rim of the vessel,
in no case less than one-inch.
B. Approved
Backflow Prevention Device: The term Approved backflow
prevention device shall mean devices which have
passed laboratory and field evaluation tests performed
by a recognized testing organization which has demonstrated
their competency to perform such tests to the California
Department of Health Services.
C. Approved
Water Supply: The term approved water supply
means any water supply whose potability is regulated by
a State or local health agency.
D. Auxiliary
Supply: The term auxiliary supply means any
water supply on or available to the premises other than
the approved water supply.
E. AWWA Standards:
The term AWWA Standard means an official standard
developed and approved by the American Water Works Association
(AWWA).
F. Backflow:
The term backflow shall mean a flow condition,
caused by a differential in pressure that causes the flow
of water or other liquids, gases, mixtures or substances
into the distributing pipes of a potable supply of water
from any source or sources other than an approved water
supply source. Backsiphonage is one cause of backflow.
Back pressure is the other cause.
G. Contamination:
The term contamination means a degradation
of the quality of the potable water by any foreign substance
which creates a hazard to the public health, or which
may impair the usefulness or quality of the water.
H. Cross-Connection:
The term cross-connection as used in this
Ordinance means any unprotected actual or potential connection
between a potable water system used to supply water for
drinking purposes and any source or system containing
unapproved water or a substance that is not or cannot
be approved as safe, wholesome, and potable. By-pass arrangements,
jumper connections, removable sections, swivel or changeover
devices, or other devices through which backflow could
occur, shall be considered cross-connections.
I. Double Check
Valve Assembly: The term double check valve assembly
means an assembly of at least two independently acting
check valves including tightly closing shut-off valves
on each side of the check valve assembly and test cocks
available for testing the watertightness of each check
valve.
J. Health Agency:
The term health agency means the California
Department of Health Services, or the local health agency
with respect to a small water system.
K. Local Health
Agency: The term local health agency means
the county or city health authority.
L. Person: The
term person means an individual, corporation,
company, association, partnership, municipality, public
utility, or other public body or institution.
M. Premises:
The term premises means any and all areas
on a water users property which are served by the
public water system.
N. Public Water
System: The term public water system means
a system for the provision of piped water to the public
for human consumption that has five or more service connections
or regularly serves an average of 25 individuals daily
at least 60 days out of the year.
O. Reclaimed
Water: The term reclaimed water means a wastewater
which, as a result of treatment, is suitable for uses
other than potable use.
P. Reduced Pressure
Principle Backflow Prevention Device: The term reduced
pressure principle backflow prevention device means
a device incorporating two or more check valves and an
automatically operating differential relief valve located
between the two checks, a tightly closing shut-off valve
on each side of the check valve assembly, and equipped
with necessary test cocks for testing.
Q. Service Connection:
The term service connection refers to the
point of connection of a users piping to the water
suppliers facilities.
R. Water Supplier:
The term water supplier means the person who
owns or operates the approved water supply system.
S. Water User:
The term water user means any person obtaining
water from an approved water supply system.
SECTION 3: CROSS-CONNECTION PROTECTION REQUIREMENTS
A. General Provisions:
- Unprotected cross-connections with the public water
supply are prohibited.Whenever backflow protection has
been found necessary, the Association will require the
water user to install an approved backflow prevention
device by and at his expense for continued services
or before a new service will be granted.
- Wherever backflow protection has been found necessary,
on a water supply line entering a water users
premises, then any and all water supply lines from the
Associations mains entering such premises, buildings,
or structures shall be protected by an approved backflow
prevention device. The type of device to be installed
will be in accordance with the requirements of this
ordinance.
B. Where Protection
is Required:
- Each service connection from the Association water
system for supplying water to premises having an auxiliary
water supply shall be protected against backflow of
water from the premises into the public water system
unless the auxiliary water supply is accepted as an
additional source by the Association, and is approved
by the public health agency having jurisdiction.
- Each service connection from the Association water
system for supplying water to any premises on which
any substance is handled in such fashion as may allow
its entry into the water system shall be protected against
backflow of the water from the premises into the public
system. This shall include the handling of process waters
and waters originating from the Association water system
which have been subjected to deterioration in sanitary
quality.
- Backflow prevention devices shall be installed on
the service connection to any premises having (a) internal
cross-connections that cannot be permanently corrected
and controlled to the satisfaction of the state or local
health department and the Association, or (b) intricate
plumbing and piping arrangements or where entry to all
portions of the premises is not readily accessible for
inspection purposes, making it impracticable or impossible
to ascertain whether or not cross-connections exist.
C. Type of Protection
Required:
The type of protection that shall be provided to prevent
backflow into the approved water supply shall commensurate
with the degree of hazard that exists on the consumers
premises. The type of protective device that may be
required (listing in an increasing level of protection)
includes: Double Check Valve Assembly (DC), Reduced
Pressure Principle Backflow Prevention Device (RP),
and an Air-gap separation (AG). The water user may choose
a higher level of protection than required by the Association.
- The minimum types of backflow protection required
to protect the approved water supply, at the users
water connection to premises with varying degrees of
hazard are given in Table 1. Situations which are not
covered in Table 1 shall be evaluated on a case by case
basis and the appropriate backflow protection shall
be determined by the Association or health agency.
Table
1
TYPE
OF BACKFLOW REQUIRED
Degrees of Hazard
Minimum Type of Backflow Prevention
SEWAGE
AND HAZARDOUS SUBSTANCES
Premises where
the public water system is used to supplement the reclaimed
water supply.
AG
Premises where there are wastewater pumping and/or treatment
plants and there is no interconnection with the potable
water system. This does not include a single family residence
that has a sewage lift pump. A RP may be provided in lieu
of an AG if approved by the health agency and the Association.
AG
Premises where reclaimed water is used and there is no
interconnection with the potable water system. A RP may
be provided in lieu of an AG if approved by the health
agency and the Association.
AG
Premises where hazardous substances are handled in any
manner in which the substances may enter a potable water
system. This does not include a single family residence
that has a sewage lift pump. A RP may be provided in lieu
of an AG if approved by the health agency and the Association.
AG
Premises where there are irrigation systems into which
fertilizers, herbicides, or pesticides are, or can be,
injected.
AUXILIARY
WATER SUPPLIES
Premises where
there is an unapproved auxiliary water supply which is
interconnected with the public water system. A RP or DC
may be provided in lieu of an AG if approved by the health
agency and the Association.
AG
Premises where
there is an unapproved auxiliary water supply and there
are no interconnections with the public water system.
A DC may be provided in lieu of an RP if approved by the
health agency and Association.
RP
Degrees of Hazard
Minimum Type of Backflow Prevention
FIRE
PROTECTION SYSTEMS
Premises where
the fire system is directly supplied from the public water
system and there is an unapproved auxiliary water supply
on or to the premises (not interconnected).
DC
Premises where
the fire system is supplied from the public water system
and interconnected with an unapproved auxiliary water
supply. A RP may be provided in lieu of an AG if approved
by the health agency and Association.
AG
Premises where
the fire system is supplied from the public water system
and where either elevated storage tanks or fire pumps
which take suction from the private reservoirs or tanks
are used.
DC
DOCKSIDE
WATERING POINTS AND MARINE FACILITIES
DC
Pier hydrants
for supplying water to vessels for any purpose.
DC
Premises where
there are marine facilities.
RP
Premises where
entry is restricted so that inspections for cross-connections
cannot be made with sufficient short notice to assure
that cross-connections do not exist.
RP
Premises where
there is a repeated history of cross-connections being
established or re-established.
RP
2. Two or more
services supplying water from different street mains to
the same building, structure, or premises through which
an interstreet main flow may occur, shall have at least
a standard check valve on each water service to be located
adjacent to and on the property side of the respective
meters. Such check valve shall not be considered adequate
if backflow protection is deemed necessary to protect
the Associations mains from pollution or contamination;
in such cases the installation of approved backflow devices
at such service connections shall be required.
SECTION 4: BACKFLOW PREVENTION DEVICES
A. Approved
Backflow Prevention Devices:
- Only backflow prevention devices which have been approved
by the Association shall be acceptable for installation
by a water user connected to the Associations
potable water system.
- The Association will provide, upon request, to any
affected customer with a list of approved backflow prevention
devices.
B. Backflow
Prevention Device Installation:
Backflow prevention
devices shall be installed in a manner prescribed in Section
7603, Title 22 of the California Administrative Code.
Location of the devices should be as close as practical
to the users connection. The Association shall have
the final authority in determining the required location
of a backflow prevention device.
- Air-Gap Separation (AG): The air-gap separation shall
be located on the users side and as close to the
service connection as is practical. All piping from
the service connection to the receiving tank shall be
above grade and be entirely visible. No water use shall
be provided from any point between the service connection
and the air-gap separation. The water inlet piping shall
terminate a distance of at least two (2) pipe diameters
of the supply inlet, but in no case less than one (1)
inch above the overflow rim of the receiving tank.
- Reduced Pressure Principle Backflow Prevention Device
(RP): The approved reduced pressure principle backflow
prevention device shall be installed on the users
side of and as close to the service connection as is
practical. The device shall be installed a minimum of
twelve inches (12) above grade and not more than
thirty-six inches (36) above grade measured from
the bottom of the device and with a minimum of twelve
inches (12) side clearance. The device shall be
installed so that it is readily accessible for maintenance
and testing. Water supplied from any point between the
service connection and the RP device shall be protected
in a manner approved by the Association.
- Double Check Valve Assembly (DC): The approved double
check valve assembly shall be located as close as practical
to the users connection and shall be installed
above grade, if possible, and in a manner where it is
readily accessible for testing and maintenance. If a
double check valve assembly is put below grade it must
be installed in a vault such that there is a minimum
of six inches (6) between the bottom of the vault
and the bottom of the device, so that the top of the
device is no more than a maximum of eight inches (8)
below grade, so there is a minimum of six inches of
clearance between the side of the device with the test
cocks and the side of the vault. Special consideration
must be given to double check valve assemblies of the
Y type. These devices must be installed
on their side with the tests cocks in a
vertical position so that either check valve may be
removed for service without removing the device. Vaults
which do not have an integrated bottom must be placed
on a three-inch (3) layer of gravel.
C. Backflow
Prevention Device Testing and Maintenance:
- The owners of any premises on which, or on account
of which, backflow prevention devices are installed,
shall have the devices tested by a person who has demonstrated
their competency in testing of these devices to the
Association. Backflow prevention devices must be tested
at least annually and immediately after installation,
relocation or repair. The Association may require a
more frequent testing schedule if it is determined to
be necessary. No device shall be placed back in service
unless it is functioning as required. A report in a
form acceptable to the Association shall be filed with
the Association each time a device is tested, relocated,
or repaired. These devices shall be serviced, overhauled,
or replaced whenever they are found to be defective
and all costs of testing, repair, and maintenance shall
be borne by the water user.
- The Association will supply affected water users with
a list of persons acceptable to the Association to test
backflow prevention devices. The Association will notify
affected customers by mail when annual testing of a
device is needed and also supply users with the necessary
forms which must be filled out each time a device is
tested or repaired.
D. Backflow
Prevention Device Removal:
- Approval must be obtained from the Association before
a backflow prevention device is removed, relocated,
or replaced.
Removal: The use of a device
may be discontinued and the device removed from service
upon presentation of sufficient evidence to the Association
to verify that a hazard no longer exists or is not
likely to be created in the future;
Relocation:
A device may be relocated following confirmation by
the Association that the relocation will continue
to provide the required protection and satisfy installation
requirements. A retest will be required following
the relocation of the device;
Repair:
A device may be removed for repair, provided the water
use is either discontinued until repair is completed
and the device is returned to service, or the service
connection is equipped with other backflow protection
approved by the Association. A retest will be required
following the repair of the device; and,
Replacement: A device may be
removed and replaced provided the water use is discontinued
until the replacement device is installed. All replacement
devices must be commensurate with the degree of hazard
involved.
SECTION
5: USER SUPERVISOR
At each premises
where it is necessary, in the opinion of the Association,
a user supervisor shall be designated by and at the expense
of the water user. This user supervisor shall be responsible
for the monitoring of the backflow prevention devices
and for avoidance of cross connections. In the event of
contamination or pollution of the drinking water system
due to a cross-connection on the premises, the Association
shall be promptly notified by the user supervisor so that
appropriate measures may be taken to overcome the contamination.
The water user shall inform the Association of the user
supervisors identity on, as a minimum, an annual
basis and whenever a change occurs.
SECTION
VI: ADMINISTRATIVE PROCEDURES
A. Water System
Survey:
- The Association shall review all requests for new
services to determine if backflow protection is needed.
Plans and specifications must be submitted to the Association
upon request for review of possible cross-connection
hazards as a condition of service for new service connections.
If it is determined that a backflow prevention device
is necessary to protect the public water system, the
required device must be installed before service will
be granted.
- The Association may require an on-premise inspection
to evaluate cross-connection hazards. The Association
will transmit a written notice requesting an inspection
of his piping system shall be required to install the
backflow prevention device the Association considers
necessary.
- The Association may, at its discretion, require a
reinspection for cross-connection hazards of any premise
to which it serves water. The Association will transmit
a written notice requesting an inspection appointment
to each affected water user. Any water user who cannot
or will not allow an on-premise inspection of his piping
system shall be required to install the backflow prevention
device the Association considers necessary.
B. Customer
Notification Device Installation:
- The Association will notify the water user of the
survey findings, listing the corrective actions to be
taken if any are required. A period of 60 days will
be given to complete all corrective actions required,
including installation of backflow prevention devices.
- A second notice will be sent to each water user who
does not take the required corrective actions prescribed
in the first notice within the 60 days period allowed.
The second notice will give the water user a two week
period to take the required corrective action. If no
action is taken within the 2 week period the Association
may terminate water service to the affected water user
until the required corrective actions are taken.
SECTION
7: WATER SERVICE TERMINATION
A. General:
When the Association encounters water uses that represent
a clear and immediate hazard to the potable water supply
that cannot be immediately abated, the Association shall
institute the procedure for discontinuing the Association
water service.
B. Basis for
Termination: Conditions or water uses that create a basis
for water service termination shall include, but are not
limited to, the following items:
- Refusal to install a required backflow prevention
device,
- Refusal to test a backflow prevention device,
- Refusal to repair a faulty backflow prevention device,
- Refusal to replace a faulty backflow prevention device,
- Direct or indirect connection between the public water
system and a sewer line,
- Unprotected direct or indirect connection between
the public water system and a system or equipment containing
contaminants,
- Unprotected direct or indirect connection between
the public water system and an auxiliary water system,
- A situation which presents an immediate health hazard
to the public water system.
C. Water Service
Termination Procedures:
- For conditions 1, 2, 3, or 4, the Association will
terminate service to a customers premise after
2 written notices have been sent specifying the corrective
action needed and the time period in which it must be
done. If no action is taken within the allowed time
period water service may be terminated.
- For conditions 5, 6, 7, or 8, the Association will
take the following steps:
a. Make reasonable effort to advise water user of
intent to terminate water service
b.Terminate water supply and lock service valve. The
water service will remain inactive until correction
of violations has been approved by the Association.
SECTION 8: SEVERABILITY
If any section,
subsection, subdivision, paragraph, sentence, clause,
or phrase of this Policy, or any part thereof, is for
any reason held to be invalid, such decision shall not
affect the validity of the remaining portions of this
Policy or any part thereof. The Board hereby declares
that it would have passed each section, subsection, subdivision,
paragraph, sentence, clause, or phrase thereof, irrespective
of the fact that any one or more sections, subsections,
subdivisions, paragraphs, sentences, clauses, or phrases
be declared invalid.
SECTION 9: EFFECTIVE
DATE
This Policy
effective April 2004.
|